NTU_FROM_P_BASIC
This function computes side-1 transfer units from side-1 temperature effectiveness and heat-capacity ratio for basic exchanger configurations. It supports analytical and numerical inversions depending on subtype.
The solved quantity is \mathrm{NTU}_1 = f^{-1}(P_1, R_1, \text{subtype}).
Excel Usage
=NTU_FROM_P_BASIC(p_one, r_one, basic_subtype)
p_one(float, required): Thermal effectiveness with respect to stream 1 (-).r_one(float, required): Heat capacity ratio with respect to stream 1 (-).basic_subtype(str, optional, default: “crossflow”): Basic exchanger subtype (-).
Returns (float): Thermal number of transfer units with respect to stream 1 (-).
Example 1: NTU for counterflow basic exchanger
Inputs:
| p_one | r_one | basic_subtype |
|---|---|---|
| 0.975 | 0.1 | counterflow |
Excel formula:
=NTU_FROM_P_BASIC(0.975, 0.1, "counterflow")
Expected output:
3.98477
Example 2: NTU for parallel flow basic exchanger
Inputs:
| p_one | r_one | basic_subtype |
|---|---|---|
| 0.55 | 0.5 | parallel |
Excel formula:
=NTU_FROM_P_BASIC(0.55, 0.5, "parallel")
Expected output:
1.16198
Example 3: NTU for crossflow basic exchanger
Inputs:
| p_one | r_one | basic_subtype |
|---|---|---|
| 0.85 | 0.7 | crossflow |
Excel formula:
=NTU_FROM_P_BASIC(0.85, 0.7, "crossflow")
Expected output:
5.20718
Example 4: NTU for crossflow mixed fluids
Inputs:
| p_one | r_one | basic_subtype |
|---|---|---|
| 0.65 | 0.3 | crossflow, mixed 1&2 |
Excel formula:
=NTU_FROM_P_BASIC(0.65, 0.3, "crossflow, mixed 1&2")
Expected output:
1.29197
Python Code
Show Code
from ht.hx import NTU_from_P_basic as hx_NTU_from_P_basic
def NTU_from_P_basic(p_one, r_one, basic_subtype='crossflow'):
"""
Solve NTU for a basic exchanger from effectiveness and capacity ratio.
See: https://ht.readthedocs.io/en/latest/ht.hx.html
This example function is provided as-is without any representation of accuracy.
Args:
p_one (float): Thermal effectiveness with respect to stream 1 (-).
r_one (float): Heat capacity ratio with respect to stream 1 (-).
basic_subtype (str, optional): Basic exchanger subtype (-). Valid options: Counterflow, Parallel, Crossflow, Crossflow Approximate, Crossflow Mixed 1, Crossflow Mixed 2, Crossflow Mixed 1&2. Default is 'crossflow'.
Returns:
float: Thermal number of transfer units with respect to stream 1 (-).
"""
try:
result = hx_NTU_from_P_basic(P1=p_one, R1=r_one, subtype=basic_subtype)
return result
except Exception as e:
return f"Error: {str(e)}"Online Calculator